Structure and function
Function
3
29 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
3.3 Function
3.3.1 Parameter sets
The detection behavior of the point detectors is influenced by the parameter sets
so that it can be specifically adjusted to the fire phenomena and environmental
conditions to be expected in the environment to be monitored.
All parameter sets are programmed in the point detectors. During commissioning,
the optimum parameter set must be selected for the conditions at the place of
installation.
On a FDnet detector line, the parameter set must always be set explicitly.
You can select and set the parameter sets as follows:
Using the 'SintesoWorks' software
Directly on your fire detection system (only within the same sensor mode)
You will find a description of the exact procedure for selecting and setting the
parameters in the relevant documentation.
Please note the chapter 'Applicable documents'.
3.3.1.1 Parameter sets for fire detection
The detection behavior of the detectors is influenced by the parameter sets for fire
detection, so that it can be specifically adjusted to the fire phenomena and
environmental influences expected in the area requiring monitoring.
All parameter sets for fire detection are programmed in the detectors. During
commissioning, the optimum parameter set must be selected for the conditions at
the place of installation.
Always use the suitable parameter set for fire for the corresponding application.
The default device parameter set is not always the suitable parameter set.
3.3.1.2 Parameter sets for 'Technical CO Alarm'
Regardless of the parameter sets for fire detection, the CO detection behavior of
the detector can be influenced by the separate parameter sets for CO and set
specifically to the environmental influences expected in the area requiring
monitoring.
All parameter sets for CO are programmed in the point detector. During
commissioning, the optimum parameter set can be selected for the conditions at
the place of installation.
Unlike the parameter sets for fire detection, the parameter set for CO does not
necessarily have to be configured. Provided that a fire detection system allows the
parameter set for CO to be configured, we would recommend configuring it.
The neural fire detector FDOOTC241 cannot be operated as a pure CO detector.
You must always select a parameter set for fire detection as well as the
parameter set for CO.