4.3.2 Parameter sets for the 'Technical CO Alarm'
4.3.2.1 Description
(Parameter set numbers in brackets)
Robust EU1 (0):
Default device parameter set with a static alarm threshold of 60 ppm CO. This
parameter set has a large compensation range and rapid compensation. Warning
level 3 is not output in the default device parameter set.
Balanced EU2 (1):
This parameter set corresponds to the dynamic CO alarm thresholds according to
EN 50291. The parameter set has a small compensation range.
Static 40 (4):
This parameter set has a static alarm threshold of 40 ppm CO. The parameter set
has a small compensation range.
Static 50 (5):
This parameter set has a static alarm threshold of 50 ppm CO. The parameter set
has a small compensation range.
Static 60 (6):
This parameter set has a static alarm threshold of 60 ppm CO. The parameter set
has a small compensation range.
Balanced US1 (7):
This parameter set corresponds to the dynamic CO alarm thresholds according to
UL 2034. The parameter set has a small compensation range.
See also
4.3.2.2 Application
No.
Name
Risk of increased
concentration of CO
(risk of damage to
persons)
CO concentration
Room geometry
Deceptive
phenomena
Compensation
range
small …
large
low …
high
simple …
complex
few …
many
small …
large
0
'Robust EU1'
1
'Balanced EU2'
1
4
'Static 40'
5
'Static 50'
6
'Static 60'
7
'Balanced US1'
1
1
Time-dependent