Planning
Technical Ambient Supervision Message
4
60 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
4.4 Technical Ambient Supervision Message
NOTICE
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
The signals for CO detection or temperature recording must not be used to
control fire detection equipment in accordance with EN 54-2.
The 'Technical Ambient Supervision Message' function is only supported by
FDOOTC241 neural fire detectors with ES 43.
4.4.1 Ambient features
In markets where the use of the 'Technical Ambient Supervision Message' is
permitted, the point detector can be positioned above or near objects which require
the operating temperature or CO concentration to be monitored to prevent
damage.
The following ambient conditions are detected in 'Technical Ambient Supervision
Message' mode:
An increase or decrease in temperature
An increase in CO concentration
You can set the following parameters using the 'SintesoWorks' software on the
control panel:
CO concentration or temperature threshold value
Alarming when the temperature threshold value is exceeded or undershot
Alarming when the CO concentration threshold value is exceeded
Hysteresis range
You will find more detailed information in the fire detection system documentation.