Structure and function
Overview
3
24 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
3.1.3 Features of the 'Technical Ambient Supervision Message'
In 'Technical Ambient Supervision Message' mode, the point detector FDOOTC241
can detect an increase in temperature or CO concentration caused by hysteresis
above a specified threshold value.
The control panel is used to configure the parameters.
Figure 4: Signal processing by the 'Technical Ambient Supervision Message'
NOTICE
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
The signals for CO detection or temperature recording must not be used to
control fire detection equipment in accordance with EN 54-2.
The 'Technical Ambient Supervision Message' function is only supported by
FDOOTC241 neural fire detectors with ES 43.
See also
Technical Ambient Supervision Message [ 60]
°C
CO
Warning level for
Technical Ambient
Supervision Alarm
Result
Signal analysis
Sensory
Algorithms
Environment:
CO or
temperature