Planning
Fire detection
4
49 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
Suppression CO (12)
Thanks to its very robust behavior, this parameter set is particularly suited for
rooms where deceptive phenomena such as vapor, cigarette smoke or exhaust
fumes can be expected. It reacts in a very robust way to the deceptive
phenomenon vapor. In the event of smoldering fires or fires in rooms where
cleaning products are stored, the parameter set reacts quicker than the
'Suppression (5)' parameter set as it takes the CO concentration into account.
High Compensation (7)
This parameter set reacts in the same way as the 'Robust (2)' parameter set,
however, the compensation range is twice as large. This parameter set is thus
especially suited for rooms in which a lot of dust and other deposits can be
expected during longer periods.
Robust (2)
The priority of the 'Robust (2)' parameter set is on robust response. The sensitivity
is the same as with the 'Suppression (5)' parameter set; however, deceptive
phenomena are not explicitly analyzed and suppressed. It is thus particularly suited
to application in rooms where deceptive phenomena such as cigarette smoke or
dust can be expected. The 'Robust (2)' parameter set is suitable for higher rooms
in comparison to the 'Suppression (5)' parameter set.
Balanced (4)
The 'Balanced (4)' parameter set displays a balanced response behavior in its
response to fires and robustness to deceptive phenomena. It reacts faster with
open fires. It reacts slower with vapor, cigarette smoke or smoldering fires.
Balanced CO (10):
This parameter set displays a balanced response behavior in its response to fires
and robustness to deceptive phenomena. It reacts faster with open fires. It reacts
slower with vapor or cigarette smoke. In the event of smoldering fires or fires in
cleaning rooms, the parameter set reacts quicker than the 'Balanced (4)' parameter
set as it takes the CO concentration into account.
Thanks to the fact that three criteria are evaluated (smoke, heat and CO
concentration), this gives particular robustness to deceptive phenomena when
compared with more sensitive parameter sets.
Fast Response (6)
The parameter set reacts in a fast and highly sensitive manner. It is especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
High Sensitive Fast (9)
This parameter set is suited for applications requiring very high sensitivity levels. It
reveals a significantly higher optical and thermal sensitivity than 'Fast Response'.
This parameter set is also suited for applications that can otherwise only be
covered with special detectors.
Download 1 (14)/Download 2 (15)
Application-specific parameter sets that can be loaded directly onto the point
detector.
All parameter sets except for 8 comply with standards EN 54-7 and CEA 4021.