Mounting / Installation
Collective and addressable detector base FDB201/221
5
65 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
5.2 Collective and addressable detector base
FDB201/221
Route the recess-mounted cable or surface-mounted cable with an outer
diameter of max. 6 mm directly into the detector base.
Ensure that the cables are flat on the bottom of the detector base. This way,
they do not pose an obstruction when inserting the detector.
Figure 11: Mounting of detector bases FDB201/FDB201-AA and FDB221/FDB221-AA
1 Detector base
5.3 Flat detector base FDB202/222
The cables are routed recess-mounted through detector base FDB202/222.
The cables must be placed flat on the bottom of the detector base so that they
do not hamper insertion of the detector.
Figure 12: Mounting of detector base FDB202/FDB222
1 Detector base
FDB201/FDB221
FDB201-AA/
FDB221-AA
max. 4mm
Ø
max. 6mm
Ø
min. 46
max. 79
1
FDB202/FDB222
max. 4mm
Ø
min. 46
max. 79
1