Structure and function
Function
3
36 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
External alarm indicators
The table below describes the flashing behavior of external alarm indicators in
combination with a point detector whose product version corresponds to the title of
this chapter.
Operating condition
Flashing mode
Graphic
Alarm/Active
Display priority: 1
EAI flashes red every
second
Fault
1
Display priority: 2
EAI off
Normal
Display priority: 3
Configuration 1
(
device default
)
EAI off
Configuration 2 EAI flashes red every
10 seconds
1
Or 'Configuration 1' mode active.
The display priority ensures that important messages are prioritized in the flashing
behavior. Highest display priority: 1.
Example: If a detector is displaying 'Fault' and then an alarm is detected, the
flashing mode will change from 'Fault' to 'Alarm'.
Information about the product version of your point detector can be found in the
'Product version ES' chapter.
3.3.8 Connection for external alarm indicators
You can connect two external alarm indicators to the detector. One external alarm
indicator can be connected to any detector in the FDnet. The trigger for activating
the alarm indicator can be programmed at the control panel.
Instead of an optical alarm indicator that flashes in the event of an alarm, the
sounder base is provided with an acoustic alarm indicator.
See also
Addressed sounder base FDSB291 [ 41]
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]
t
0
1
2
3
4
5
6
7
8
9
10
12
11
[s]