Mounting / Installation
Base attachment humid FDB293
5
69 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
5.6 Base attachment humid FDB293
For mounting in wet rooms, the base attachment humid FDB293 is used.
To seal the cables, especially tight cable glands are used.
Figure 15: Mounting of detector base on base attachment humid FDB293
1 Base attachment humid
2 Detector base
5.7 Base attachment wet FDB295
The 'base attachment wet FDB295' is for surface-mounted feed lines in humid
and cold environments.
It is not possible to remove the detector using the detector tester
FDUD291/detector exchanger and tester FDUD292/intelligent detector tester
FDUD293.
The cables are inserted using M20 x 1.5 metal cable glands (Fig. 3).
Protective cages DBZ1194/FDBZ294 can be installed on 'base attachment wet
FDB295'.
– Protective cage DBZ1194 (Fig. 3) protects the detector against mechanical
damage.
– EMC-protective cage FDBZ294 (Fig. 4) protects the detector against
mechanical damage and electromagnetic fields.
Note the dimensions of the protective cages (Fig. 3).
To connect detector heating unit FDBH291, see chapter: 'Connection of the
detector heating unit'.
max. 4mm
Ø
max. 4mm
Ø
FDB293
FDB2x1
FDB2x1-AA
FDB2x2
1
2