5
Mounting / Installation
Mounting
58
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
5.2
Mounting
5.2.1
Adapting the front indicator to the installation position
The aspirating smoke detector can be installed rotated by 180° if required. The
front indicator must then also be installed rotated by 180°.
180°
8x
8x
1
2
4
3
Adapting the front indicator to the installation position
The housing cover has been removed (step 1).
1. Loosen the 8 screws on the inside of the housing cover (step 2).
2. Rotate the front indicator by 180° (step 3).
3. Fasten the front indicator to the housing cover using the 8 screws (step 4).
The front indicator is adapted to the installation position.