Specifications
9
Technical data for FDA241, FDA221
107
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
Pipe system
Pipe outer diameter
25 mm
Inner diameter of pipe
21 mm
Maximum piping lengths for FDA241:
Single line
FDA241: 60 m
Branched lines
FDA241: 2 x 60 m
Maximum piping lengths for FDA221:
Single line
30 m
Branched lines
2 x 25 m
Monitored surface
The maximum permissible surface depends on the locally valid regulations!
Maximum surface:
FDA241
800 m²
FDA221
500 m²
Compatibility (FDCC221S installed)
Compatible with fire control panels
FC20xx/FC72x
Ambient conditions
Operating temperature
-20…+60 °C
Storage temperature
-30…+70 °C
Air humidity
5…95 % rel.,
no moisture
condensation
Protection category (IEC 60529):
FDA241
IP30
FDA221
IP30
Mechanical data
Weight
approx. 1.5 kg
Housing material
ABS/PC
Housing color
∽RAL
9010 pure white
Standards
European standards
EN 54-20 A, B, C
EN 54-17 with
FDCC221S installed