Structure and function
3
Function
35
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
3.5.1.1
Danger levels
The aspirating smoke detector can transmit the following danger levels to the fire
control panel:
Symbol
Danger level
_
1
1
2
3
3
Designation
_
Inspect
Prealarm
Fire 1
Fire 2
Configuration in the
fire detection
installation
_
Sensor 1
Sensor 2
Meaning
No danger Possible danger
Warning
Alarm
Alarm and extinguishing
Alarm level: Fire 2
Comment
Normal
Check situation
Possible
danger
Fire
The highest danger level 3 has been
reached and the conditions for
activating extinguishing are satisfied.
1
If danger level 1 is frequently transmitted, check whether another sensitivity
setting is more suitable.
The evaluation of the danger level and the decisions to be taken (e.g. activation of
remote transmission) are configured in the fire detection system.
3.5.1.2
Interface to service devices
A port with the MC link (maintenance and commissioning link) is installed on
communication transponder FDCC221S.
Using this interface, it is possible to read data from the device with the 'FDUD292
detector exchanger and tester' or the 'FDUD293 intelligent detector tester'.
You will find more information in documents 007227 and 009718.