7SR10 Description of Operation
©2018 Siemens Protection Devices Limited Chapter 1 Page 48 of 77
3.4.13 Power Protection: Power (32)
Two under/over power elements are provided and can measure real, reactive or apparent power.
Gn 32-n Setting
sets the pick-up power level for the element.
Under-power or over-power operation can be set by the
Gn 32-n Operation
setting.
Gn 32-n 1ph/3ph Power allows the settings to be based on any one phase exceeding the power pick up level or
on the total power of all three phases.
An output is given after elapse of the
Gn 32-n Delay
setting.
Operation of the under/over power elements can be inhibited when:
The measured current is below the
Gn 32-n U/C Guard
setting
A VT Fail condition is detected
Inhibit 32-n
A binary or virtual input.
V
1
I
L1
V
2
V
3
I
L3
I
L2
&
Enabled
Enabled
<
&
<
<
&
En.
Inhibit
VT Fail
&
+W
-VAr
-W
-VAr
-W
+VAr
+W
+VAr
Gn32-n: Operation: Under/Over
Gn 32-n U/C Guard
Setting
Gn 32-n Delay
Gn32-n: 1ph/3ph Power
Gn32-n: Power: P, Q, R
Gn32-n: Direction
Gn32-n: Setting
Gn 32-n U/C
Guarded
Gn 32-n VTS
Action
Gn 32-n Element
32-n
General Pickup
Inhibit 32-n
Figure 3-27 Logic Diagram: Power Protection (32)
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...