7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 24 of 52
2.8 50 Instantaneous Overcurrent
2.8.1 Reference
Parameter
Value
Is
Setting
0.05, 0.06… 2.5, 2.55… 50xI
n
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.8.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 % I
s
,
±
5 % or
±
1 % I
n
Reset level
≥
95 % I
op
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
Variation
-10 °C to +60 °C
≤
5 %
f
nom
± 5 %
≤
5 %
2.8.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
#
0 to 2 xI
s
: 35 ms,
±
10 ms
0 to 5 xI
s
: 25 ms,
±
10 ms
t
op
Operate time following delay
t
basic
+ t
d
,
±
1 % or
±
10 ms
Repeatability
±
1 % or
±
10 ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms
#
The operating timings are measured on the basis of fundamental measurement algorithm, with protection
functions and communication ports configured in the relay.
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...