7SR10 Technical Manual
Chapter 4 - Page 62 of 78
© 2018 Siemens Protection Devices
The default analog input event buffer size is set 30. The analog input event mode is set to Most Recent, only most
recent event for each point is stored.
Analog inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
0 Frequency
0,3
2
4
100.000
1.000
1 Vab Primary
0,3
2
4
0.010
100.000
2 Vbc Primary
0,3
2
4
0.010
100.000
3 Vca Primary
0,3
2
4
0.010
100.000
4 Va Primary
0,3
2
4
0.010
100.000
5 Vb Primary
0,3
2
4
0.010
100.000
6 Vc Primary
0,3
2
4
0.010
100.000
7 Va Secondary
0,3
2
4
10.000
1.000
8 Vb Secondary
0,3
2
4
10.000
1.000
9 Vc Secondary
0,3
2
4
10.000
1.000
21 Vzps
0,3
2
4
10.000
1.000
22 Vpps
0,3
2
4
10.000
1.000
23 Vnps
0,3
2
4
10.000
1.000
31 Ia Primary
0,3
2
4
1.000
100.000
32 Ib Primary
0,3
2
4
1.000
100.000
33 Ic Primary
0,3
2
4
1.000
100.000
34 Ia Secondary
0,3
2
4
100.000
0.100
35 Ib Secondary
0,3
2
4
100.000
0.100
36 Ic Secondary
0,3
2
4
100.000
0.100
37 Ia Nominal
0,3
2
4
100.000
0.100
38 Ib Nominal
0,3
2
4
100.000
0.100
39 Ic Nominal
0,3
2
4
100.000
0.100
43 In Primary
0,3
2
4
1.000
100.000
44 In Secondary
0,3
2
4
100.000
0.100
45 In Nominal
0,3
2
4
100.000
0.100
46 Ig Primary
0,3
2
4
1.000
100.000
47 Ig Secondary
0,3
2
4
1000.000
0.100
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...