7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 44 of 52
2.19 64H Restricted Earth Fault Protection
2.19.1 Reference
Parameter
Value
Is
Setting
SEF Input 0.005, 0.006 … 0.100, 0.105 … 0.950xI
n
EF Input
0.05, 0.055.… 0.95xI
n
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.19.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 % Is,
±
5 % or
±
1 %xI
n
Reset level
95 % I
op
,
±
5 % or
±
0.1 %xI
n
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
Variation
-10 °C to +60 °C
≤
5 %
f
nom
± 5 %
≤
5 %
2.19.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
0 to 2xI
s
, 45 ms,
±
10 ms
0 to 5xI
s
, 35 ms,
±
10 ms
t
op
Operate time following delay
t
basic
+ t
d
,
±
1 % or
±
10 ms
Repeatability
±
1 % or
±
10 ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...