Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
108 I Phase A Max
0,3
2
4
1.000
100.000
109 I Phase B Max
0,3
2
4
1.000
100.000
110 I Phase C Max
0,3
2
4
1.000
100.000
111 P 3P Max
0,3
2
4
10.000
1000000.000
112 Q 3P Max
0,3
2
4
10.000
1000000.000
115 Isef Primary
0,3
2
4
1.000
10.000
116 Isef Secondary
0,3
2
4
1000.000
0.050
117 Isef Nominal
0,3
2
4
1000.000
0.050
135 CB Total Trip Count
0,3
1
3
1.000
1.000
136 CB Delta Trip Count
0,3
1
3
1.000
1.000
137 CB Count To AR Block
0,3
1
3
1.000
1.000
138 CB Frequent Ops Count
0,3
1
3
1.000
1.000
165 Ia Last Trip
0,3
1
3
1.000
Disabled
166 Ib Last Trip
0,3
1
3
1.000
Disabled
167 Ic Last Trip
0,3
1
3
1.000
Disabled
168 Va Last Trip
0,3
1
3
1.000
Disabled
169 Vb Last Trip
0,3
1
3
1.000
Disabled
170 Vc Last Trip
0,3
1
3
1.000
Disabled
171 In Last Trip
0,3
1
3
1.000
Disabled
172 Ig Last Trip
0,3
1
3
1.000
Disabled
173 Isef Last Trip
0,3
1
3
1.000
Disabled
174 V Phase A Max
0,3
2
4
0.010
100.000
175 V Phase B Max
0,3
2
4
0.010
100.000
176 V Phase C Max
0,3
2
4
0.010
100.000
177 V Phase AB Max
0,3
2
4
0.010
100.000
178 V Phase BC Max
0,3
2
4
0.010
100.000
179 V Phase CA Max
0,3
2
4
0.010
100.000
184 CB Wear A
0,3
1
3
100.000
1000000.000
185 CB Wear B
0,3
1
3
100.000
1000000.000
186 CB Wear C
0,3
1
3
100.000
1000000.000
187 CB Wear A Remaining
0,3
1
3
1.000
1.000
188 CB Wear B Remaining
0,3
1
3
1.000
1.000
189 CB Wear C Remaining
0,3
1
3
1.000
1.000
190 CB Wear Minimum
0,3
1
3
1.000
1.000
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...