7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 10 of 52
Type Test
Reference
Requirement
Electrical Endurance
Test
IEC 60255-1
(Ref: Std IEC 61810-1)
10000 operations at 250 V, 5 A
Table 1-15
Electrical Tests
Type Test
Reference
Requirement
Insulation Resistance IEC 60255-27
#
Insulation resistance >100 MOhm at 500 V DC
Test Duration: > 5 s
Impulse Voltage
Withstand
IEC 60255-27
#
5 kV, 1.2/50 µs, 0.5 J
5 +ve, -ve pulses
Between all terminals and case earth and any
two independent circuits.
AC Dielectric Voltage
IEC 60255-27
#
•
All case terminals connected together 2.0 kV
AC RMS, 50 Hz, 1 min between terminals of
independent circuits
•
1.0 kV AC RMS, 1 min across normally open
contacts
Slow Damped
Oscillatory Wave
IEC 60255-26
•
Common-mode test voltage:
2.5 kV peak voltage
•
Differential mode:
1.0 kV peak voltage
•
Test duration: 2 s
•
Source impedance: 200 Ω
•
Voltage oscillation frequency: 1 MHz
•
Repetition frequency: 400 Hz
Electrostatic Discharge IEC 60255-26
•
8 kV air discharge
•
6 kV contact discharge
Electrical Fast
Transient or Burst
*
IEC 60255-26
Zone A
Test severity Amplitude :
±
4 kV
Repetition frequency : 5 kHz
Surge Immunity
*
IEC 60255-26
Test Level : Zone A
Line to Line : 0.5, 1, 2 kV
Line to Earth : 0.5, 1, 2, 4 kV
Front time/Time to half-value : 1.2/50
μ
s
Source Impedance : 2 Ohm
Radiated Immunity
IEC 60255-26
Test field strength, frequency band
80 MHz to 1.0 GHz and 1.4 GHz to 2.7 GHz:
10 V/m, Test using AM: 1 kHz/80 %
Conducted Radio
Frequency Interference
IEC 60255-26
0.15 MHz to 80 MHz
10 V RMS
Dwell time: 0.5 s
Power Frequency
Magnetic Field
IEC 60255-26
30 A/m applied continuously,
300 A/m applied for 3 s
**
Conducted Emissions IEC 60255-26
0.15 MHz to 0.5 MHz, 79dB µV (quasi peak)
66 dB µ V (average)
0.5 MHz to 30 MHz, 73dB µ V (quasi peak)
60 dB µV (average)
Radiated Emissions
IEC 60255-26
30 MHz to 230 MHz, 40 dB µ V/m at
10 m measurement distance
230 MHz to 1 GHz, 47 dB µ V/m at 10 m
measurement distance
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...