7SR10, 7SR11, 7SR12 Applications Guide
© 2018 Siemens Protection Devices Limited
Chapter 7 Page 8 of 41
Section 2: Protection Functions
2.1 Time delayed overcurrent (51/51G/51N)
The 51-n characteristic element provides a number of time/current operate characteristics. The element can be
defined as either an Inverse Definite Minimum Time Lag (IDMTL) or Definite Time Lag (DTL) characteristic. If an
IDMTL characteristic is required, then IEC, ANSI/IEEE and a number of manufacturer specific curves are
supported.
IDMTL characteristics are defined as “Inverse” because their tripping times are inversely proportional to the Fault
Current being measured. This makes them particularly suitable to grading studies where it is important that only
the Relay(s) closest to the fault operate. Discrimination can be achieved with minimised operating times.
To optimise the grading capability of the relay additional time multiplier, ‘Follower DTL’ (Fig. 2.1) or ‘Minimum
Operate Time’ (Fig. 2.2) settings can be applied.
0.01
0.10
1.00
10.00
100.00
1000.00
1
10
100
1000
Current (x Is)
O
per
at
ing T
im
e (
Sec
onds
)
Time Multiplier = 1
Increasing
Time
Multiplier
0.01
0.10
1.00
10.00
100.00
1000.00
1
10
100
1000
Current (x Is)
O
per
at
ing T
im
e (
Sec
onds
)
Follower
DTL
Figure 2-1 IEC NI Curve with Time Multiplier and Follower DTL Applied
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...