7SR10 Performance Specification
© 2018 Siemens Protection Devices Limited
Chapter 3 Page 8 of 52
Table 1-9
DC Performance
Attribute
Value
Reset/Operate voltage ratio
≥ 90
%
Response time
< 9 ms
Response time when programmed to energise an output relay contact
(i.e. includes output relay operation)
< 20 ms
Table 1-10
Binary Outputs
Number
3 or 6 (2 change over contacts)
Operating Voltage
Voltage Free
Operating Mode
User selectable - Self or Hand/Electrical Reset or pulsed
Operating Time from
energizing Binary Input
< 20 ms
Making Capacity:
Carry continuously
Make and carry
(L/R
≤
40 ms and
V
≤
300 V)
5 A AC or DC
20 A AC or DC for 0.5 s
30 A AC or DC for 0.5 s
Breaking Capacity
(
≤
5 A and
≤
300 V):
AC Resistive
AC Inductive
DC Resistive
DC Inductive
1250 VA
250 VA at p.f.
≤
0.4
75 W
30 W at L/R
≤
40 ms
50 W at L/R
≤
10 ms
Disengaging time
< 20 ms
Table 1-11
Rear Communication Port
Quantity
1 No. (Optional)
Electrical connection
RS485, 2 wire electrical
Protocol Support
MODBUS RTU,
IEC 60870-5-103,
DNP 3.0
Rate
Data Transfer rate:
75 bps to 38400 bps
Table 1-12
Front Communication Port
Quantity
1 No.
Electrical connection
USB, Type B
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...