7SR10 Technical Manual
Chapter 4 - Page 48 of 78
© 2018 Siemens Protection Devices
5.3 Point List
The tables below identify all the default data points provided by the implementation of the Triangle MicroWorks, Inc.
DNP 3.0 Slave Source Code Library.
This protocol can be set to use any or all of the relays hardware interfaces (USB and RS485) where fitted. The relay
can communicate simultaneously on all ports regardless of protocol used.
The Station Address of the port being used must be set to a suitable address within the range 0 - 65534 to enable
communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting.
The information shown below is the default configuration. This can be modified using the Communications
Configuration Editor tool, refer
5.3.1 Binary Input Points
The default binary input event buffer size is set to allow 100 events.
Binary inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
1 Binary Input 1
0,2
2
2
2 Binary Input 2
0,2
2
2
3 Binary Input 3
0,2
2
2
4 Binary Input 4
0,2
2
2
5 Binary Input 5
0,2
2
2
6 Binary Input 6
0,2
2
2
7 Binary Input 7
0,2
2
2
8 Binary Input 8
0,2
2
2
9 Binary Input 9
0,2
2
2
35 Remote Mode
0,2
2
2
36 Out Of Service Mode
0,2
2
2
37 Local Mode
0,2
2
2
38 Local & Remote
0,2
2
2
40 General Trip
0,2
2
2
41 Trip Circuit Fail
0,2
2
2
42 Start/Pick-up L1
0,2
2
2
43 Start/Pick-up L2
0,2
2
2
44 Start/Pick-up L3
0,2
2
2
45 General Start/Pick-up
0,2
2
2
46 VT Fuse Failure
0,2
2
2
47 Earth Fault Forward/Line
0,2
2
2
48 Earth Fault Reverse/Busbar
0,2
2
2
49 Start/Pick-up N
0,2
2
2
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...