Technical data
10.3 Construction
SITRANS Probe LR with mA/HART
82
Operating Instructions, 05/2019, A5E32337711-AC
10.3
Construction
Process
connections
threaded connection
1.5” NPT, BSP, or G (BS EN ISO 228-1)
Antenna
polypropylene rod
hermetically sealed construction standard 100 mm (4")
shield for maximum 100 mm (4") nozzle, or optional
250 mm (10") long shield
Note
•
Check the ambient and operating temperatures under Enclosure (below) and Approvals
(Page 83) for the specific configuration you are about to use or install.
•
Approved dust-tight and water-tight conduit seals are required for outdoor Type 4X, Type
6, IP67, IP68 locations.
Enclosure
body construction
PBT (polybutylene terephthalate)
lid construction
hard-coated PEI (polyether imide)
conduit entry
2 x M20x1.5 (plastic strain relief) or 2 x 1/2" NPT
thread
ingress protection
Type 4X, Type 6, IP67, IP68 (see note below)
Weight
standard model
1)
1.97 kg (4.35 lb.)
1)
Unit with 100 mm (4") rod and adaptors
10.4
Operating conditions
Location
indoor/outdoor
Altitude
5000 m (16,404 ft) max.
Ambient temperature
−40 to +80 °C (−40 to +176 °F)
Relative humidity
suitable for outdoor
Type 4X, Type 6, IP67, IP68 enclosure
Installation category
I
Pollution degree
4
10.5
Process
temperature (at process connection)
−40 to +80 °C (−40 to +176 °F).
pressure (vessel)
maximum 3 bar, gauge (43.5 psi, gauge)
Note
Device-specific approvals
Always refer to nameplates on the device for device-specific approvals.