Commissioning
6.2 Local commissioning
SITRANS Probe LR with mA/HART
38
Operating Instructions, 05/2019, A5E32337711-AC
6.2.11.7
P010: Language
The parameter title appears in the language selected, for parameters P000 to P010. If a
language is selected, parameter titles for the Quick Start parameters are displayed in the
auxiliary reading field.
Parameter
Value
Description
P010
0
*
Numeric/None
1
English
2
German
3
French
4
Spanish
Parameter
Auxiliary reading
P000
LOCK
P001
OPERATION
P003
MEAS RESP
P004
ANTENNA
P005
UNITS
P006
EMPTY
P007
SPAN
P010
LANGUAGE
6.2.11.8
P838 Auto false echo suppression
Enable False-Echo Suppression (P837: Auto False-Echo Suppression)
P837 instructs SITRANS Probe LR to learn the echo profile at that moment, and use the
learned profile instead of the default TVT curve.
Parameter
Value
Description
P837
0
Off
1
*
Use "Learned" TVT
2
"Learn"
Set up Auto False-Echo Suppression:
●
Perform this function when the vessel is empty or nearly empty.
●
First rotate the instrument for best signal (lowest false-echo amplitude)
●
Determine distance from reference point to material level and subtract 0.5 m (1.6 ft).
●
Press PROGRAM
, then DISPLAY
.
●
Select P838, key in [distance to material level minus 0.5 m/1.6 ft], and press ENTER .
●
Select P837.
●
Press 2 and then press ENTER
. P837 will automatically revert to 1 (use Learned
TVT) after a few seconds.
●
Press PROGRAM to return to RUN mode.