Parameter assignment
7.28 Test (P900 to P924)
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC
69
7.27.5
P839 TVT hover level
Defines (in percent) how high the TVT curve is placed above the profile, relative to the
largest echo. When SITRANS Probe LR is located in the center of the vessel, lower this
parameter to prevent multiple echo detections.
Values
Range
0 to 100%
Default
40
7.28
Test (P900 to P924)
7.28.1
P900 Software revision number
Displays the software revision level.
Values (view only)
Range
0.00 to 99.99
1
Main code revision
2
Primary boot revision
3
Alternative boot revision
3
Hardware stack revision
Default
Determined by the software revision installed
7.28.2
P901 Memory test
Press ENTER
to activate the test.
Values (view only)
PASS
Memory text successful
F1
Fail RAM
F2
Fail EEPROM
F3
Fail FLASH
7.29
Measurement
7.29.1
P911 mA output value (HART/mA only)
Access this parameter to display the current value of the mA output.
Values (HART)
Range
3.6 to 22.6 (mA)
*
4 mA in HART fixed current mode
1.
Set P201 to 0 (manual).
2.
Enter a test value.
Note
P201 must be set to 0 to enable the test value to be entered at P911. After the test, restore
P201 to the previous setting.