Parameter assignment
7.8 P010 Language
SITRANS Probe LR with mA/HART
46
Operating Instructions, 05/2019, A5E32337711-AC
7.8
P010 Language
Values
0
*
Numeric/None
1
English
2
German
3
French
4
Spanish
If a language is selected, parameter titles for the parameters P000 to P010 are displayed.
7.9
P050 to P055 Volume
Note
Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly
described.
Set SITRANS Probe LR to calculate readings based on reservoir volume instead of level.
1.
Operation must be set to Level (P001 = 1).
2.
Select a vessel shape matching the monitored vessel (P050).
3.
If required, add dimensions A or L (as shown in the chart on page 45), using P052 and
P053, or, if vessel shape 9 is selected, add level and volume breakpoints in P054 and
P055.
4.
Enter the value for the maximum vessel volume in P051.
5.
Return to RUN mode: readings are now displayed in volumetric units. To select
PERCENT, press
: the displayed volume reading will be a percentage of Maximum
Volume.
7.10
P050 Vessel shape
Defines the vessel shape (see chart on next page) and allows SITRANS Probe LR to
calculate volume instead of level. The default setting for P050 is 0 (volume calculation not
required).