Parameter assignment
7.29 Measurement
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC
71
7.29.7
P999 Master reset
Note
Following a Master Reset, complete reprogramming is required.
Resets all parameters to their factory settings, with the following exceptions:
●
P000 and P069 are not reset.
●
The learned TVT curve is not lost.
Use this feature after upgrading software:
1.
Select P999.
2.
Press CLEAR
then ENTER
to clear all and initiate reset.
3.
Reset complete. (Note: Reset takes several seconds to complete.)