Parameter assignment
7.7 P007 Span (process full level)
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC
45
①
Reference point
②
Span
③
Level setup
④
Level
⑤
Empty
Note
•
Default setting is maximum range.
•
P006 and P007 are interlinked: see note attached to P007.
7.7
P007 Span (process full level)
Sets the range to be measured (referenced from Empty) in units selected at P005.
Values
Range
0.0000 to 20.00 (m)
Default
19.56 (see note below)
Enter the distance between Empty (process empty level) and Span (process full level), in
units set in P005. Span can be set at any distance above Empty level.
Note
•
Setting P006 will reset Span, if it has not previously been set to a different value.
•
The default setting for Span is based on Operation (P001) and Empty (P006). Span is set
to Empty minus 110% of blanking distance, unless Operation is set to Distance (P001 =
3). In this case, Span is set to Empty distance. For more detail on blanking, see Near
•
Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the
reference point, as this is the minimum distance detectable.