6 – 13
6.9
Troubleshooting
1)
Safety feature!
This remedy action amounts to a reversal (disabling) of a safety
precaution installed earlier. Please do ensure that such dis-
abling is now permissible / authorized!
Fixed-
mounted cir-
cuit- breaker
Draw-out
circuit-
breaker
Disturbance
Cause
Remedy
X
X
Circuit-breaker cannot be closed
and circuit-breaker
not
ready to
close.
Ready-to-close indicator shows:
1. Spring not charged
Charge spring
X
X
2. Undervoltage release not
energized
Energize undervoltage release
X
X
3. Mechanical reclosing lock-out
effective
Rectify cause of overcurrent trip-
ping and press reset button
X
X
4. Electrical closing interlock
effective
Switch off control voltage for inter-
locking
1)
X
X
5. "OFF" locked off by cylinder
lock
(accessories)
Unlock
1)
X
X
6. "OFF" locked off by
padlocks
(accessories)
Remove padlocks
1)
X
X
7. "Mechanical OFF" button
locked off
(accessories)
Unlock the "Mechanical OFF"
button
1)
X
X
8. "EMERGENCY OFF" button
engaged in operating position
(accessories)
Release "EMERGENCY OFF"
button
1)
by rotating it
X
X
9. Lockout against closing with
cubicle door open effective
(accessories)
Close cubicle door
X
X
10. Mutual mechanical circuit-
breaker interlocks effective
(accessories)
Open second circuit-breaker or rack
into disconnected
position
1)
X
X
11. Electronic overcurrent release
(trip unit) missing or incorrectly
installed
Fit electronic overcurrent release
properly
X
X
12. Shunt trip energized
De-energize shunt trip
X
X
13. Closing coil energized
Closing coil has to be de-energized
shortly for reclosing
X
14. Racking handle withdrawn
Rack circuit-breaker into discon-
nected, test or connected position,
unlatch crank and push it fully in
Summary of Contents for 3ZX1812-0WL00-0AN2
Page 91: ...9 15 S Auslösung I Auslösung S tripping I tripping ...
Page 92: ...9 16 Erdschlussauslösung Ground fault tripping ...
Page 121: ...English part continued on Page 9 60 9 45 ...
Page 135: ...English part continued on Page 9 60 9 59 ...
Page 149: ...9 73 ...
Page 307: ...19 10 Einbau Baugröße Frame size Länge L mm Length L mm I 48 II 118 III 232 1 Fitting ...
Page 317: ...20 2 Vertikal Vertical Einschubtechnik Draw out version Horizontal Horizontal ...
Page 362: ...5HOHDVH ...
Page 363: ...5HOHDVH 5 H OH D V H ...