19 – 1
19
Mutual mechanical circuit-breaker
interlocking
In the standard design there are various versions for the mutual
interlocking system available, comprising a maximum of three
circuit-breakers.
Mutual mechanical interlocking module version 1
(1)
Guide frame
(2)
Fixed-mounted breaker
19
Gegenseitige mechanische Verriegelung
Ermöglicht in der Standardausführung verschiedene Varianten der
gegenseitigen Verriegelung von maximal drei Leistungsschaltern.
Verriegelungsbaustein Version 1
(1)
Einschubrahmen
(2)
Festeinbauschalter
HINWEIS
NOTE
Für die Funktion der Verriegelung sind in der Schaltanlage Mindest-
voraussetzungen zu schaffen:
1
Bowdenzüge sind möglichst gerade, wenig gekrümmt zu ver-
legen.
2
Biegeradien des Bowdenzuges müssen >500 mm ausge-
führt sein.
3
Im Bowdenzugverlauf darf die Summe aller Krümmungswin-
kel 540° nicht überschreiten.
4
Bei vertikaler Anordnung zu verriegelnder Leistungsschalter
sollen die Verriegelungsmechaniken fluchten.
5
Zu verriegelnde Leistungsschalter müssen so angeordnet
sein, dass 2 m oder 4,5 m lange Bowdenzüge unter Einhal-
tung der in den Punkten 1. - 4. genannten Bedingungen opti-
mal verlegt werden können.
6
Die Bowdenzugverlegung muss vor der Justage der Verrie-
gelung fixiert werden (Kabelbinder o.ä.)
7
Durch die Wahl der Schaltanlagenfachbreite muss die
Justagefreiheit für die Verriegelung gewährleistet sein.
8
Öffnungen und Durchbrüche in Anlagenelementen sind so zu
gestalten, dass durchgeführte Bowdenzüge im Verlauf nicht
richtungsorientiert oder behindert werden.
For a proper function of the interlocking device, the following mini-
mum prerequisites have to be met in the switchgear:
1
Bowden wires are to laid out as straight and as unbowed as
possible.
2
Bending radii of the Bowden wires must exceed > 500 mm.
3
The total curving of the Bowden wire must not exceed 540
degrees.
4
When stacking interlocked circuit-breakers vertically, the
interlocking devices shall be in line with each other.
5
Circuit-breakers intended to be interlocked must be posi-
tioned, so that Bowden wires of 2 m or 4.5 m length can be
laid out optimally, while complying with the conditions of
paragraphs 1. to 4.
6
Before adjusting the interlocking device, the laying of
Bowden wires must be fixed, e.g. using cable ties.
7
The width of the switchgear section must be selected as wide
as necessary to ensure space for an adjustment of the inter-
locking device.
8
Openings have to be created in the switchgear components,
so that Bowden wires are not forced in their orientation or
direction and that they are not hindered in their run.
Summary of Contents for 3ZX1812-0WL00-0AN2
Page 91: ...9 15 S Auslösung I Auslösung S tripping I tripping ...
Page 92: ...9 16 Erdschlussauslösung Ground fault tripping ...
Page 121: ...English part continued on Page 9 60 9 45 ...
Page 135: ...English part continued on Page 9 60 9 59 ...
Page 149: ...9 73 ...
Page 307: ...19 10 Einbau Baugröße Frame size Länge L mm Length L mm I 48 II 118 III 232 1 Fitting ...
Page 317: ...20 2 Vertikal Vertical Einschubtechnik Draw out version Horizontal Horizontal ...
Page 362: ...5HOHDVH ...
Page 363: ...5HOHDVH 5 H OH D V H ...