9.6 Modbus Card
INSTALLATION AND CONNECTION:
The PCB SERMB is an accessory for the PV Inverter series.
The installation has to be done with the unit OFF.
Don’t install the PCB if you see damaged on it.
i
Before installing the PCB, it is necessary to configure the dip-switch as indicate on
following page. ( the factory setting are: mode 1, Baud-Rate 9600 )
i
Connect the RS485/RS422 line to the connector on front panel, as show on Fig 1.
It is suggested to use twisted cable section 0.22mm
2
, (AWG24)
*1
.
i
If in the RS485 is connected one PV Inverter only, or if the PV Inverter is the last in the
serial connection, it is necessary to set the SW3-4 to ON position.
i
If in the RS422 is connected one PV Inverter only, or if the PV Inverter is the last in the
serial connection, it is necessary to set both SW3-3 and SW3-4 to ON position.
i
Fit the PCB in the SLOT and fix the protection cover ( supply with the PV Inverter ), then
it can guarantee the additional water protection to the device.
i
Start the PV Inverter and verify the PCB.
ig.1: RS 485/RS422 connections
1
.
The GND connection can help to cancel offset problem between the devices, or it can be connected to cable shield where present to limit
the interference.
Summary of Contents for SOLEIL 3F-TL10K
Page 89: ...IV351 Rev04 Date Issue 2015 04 21 Pagina 89 di 277 FR 17 2 Diagramma efficienza ...
Page 90: ...IV351 Rev04 Date Issue 2015 04 21 Pagina 90 di 277 FR ...
Page 180: ...IV351 Rev04 Date Issue 2015 04 21 Page 180 di 277 FR 17 2 Efficiency Chart ...
Page 181: ...IV351 Rev04 Date Issue 2015 04 21 Page 181 di 277 FR ...
Page 251: ...IV351 Rev04 Ausstellungsdatum 2015 04 21 Seite 251 von 277 FR ...
Page 275: ...IV351 Rev04 Ausstellungsdatum 2015 04 21 Seite 275 von 277 FR 17 2 Wirkungsgradkurve ...
Page 276: ...IV351 Rev04 Ausstellungsdatum 2015 04 21 Seite 276 von 277 FR ...