8014868/YEF7/2014-09-02 • © SICK AG • Subject to change without notice 37
Operating instructions Distance sensors Dx35
Commissioning
8.6
Reset to factory setting
1. Switch off the supply voltage.
2. Press an hold the
select
pushbutton.
3. Hold down the
select
pushbutton and switch on the supply voltage.
4.
When all teach LEDs flash, release the
select
pushbutton.
All settings have been reset to the factory setting.
8.7
External teach functions
NOTE
You can activate or deactivate a confirmation function,
which provides a feedback about the accomplishment
of an external teach. This teach confirmation can be
activated via IO-Link or the multifunctional input MF. The
feedback is provided via Q1.
→
See Page 50, Chap-
ter 10.4.
You can perform an external teach by applying a signal to the
multifunctional input MF. The "external teach" option for the multifunctional
input MF must be selected via expert mode.
→
See Page 36,
Chapter 8.5.
The timing tolerance for the two "Move last teach point" functions is
± 20 ms. The timing tolerance is ± 30 ms for the other teach functions.
Overview of external teach functions
(continued on next page)
Teach function
Time [ms]
Move last teach point + 10 mm
60
Move last teach point – 10 mm
120
Switch off laser
200
Switch on laser
300
Teach in Q1 distance to object
400
Teach in inverted behavior for Q1 distance to object
500
Teach in Q1 near for window
600
Teach in Q1 far for window
700
Teach in Q1 object between sensor and background
800
Teach in Q1 window centering
1), 2)
900
Teach in Q2 distance to object
1000
Teach in inverted behavior for Q2 distance to object
1100
Teach in Q2 near for window
1200
Teach in Q2 far for window
1300