Row
DIP switch
Function
D
1, 2
•
Beam coding,
•
Reset to factory settings,
1)
Only applies to SP2 system plug.
Configuration information
b
To configure an SP2 system plug via DIP switches, leave all unused DIP switches in
the OFF state. Otherwise a configuration fault is output.
b
Check the parity using an SP2 system plug after setting the DIP switches. The sum
of the DIP switches of rows A, B and C set to On must be even. In case of an
uneven sum, change the setting of DIP switch 4 (row C).
b
Securely close the protective cover for the DIP switches, which is attached to the
SP2 system plug.
b
Then ensure the correct functioning of the device.
Complementary information
If the device uses functions of an SP1 system plug and then an SP2 system plug is con‐
nected, the device retains the settings and continues to operate as with the previous
system plug.
Further topics
•
•
"Configuring the restart interlock", page 71
•
"Configuring external device monitoring (EDM)", page 72
7.2
Factory settings
Table 20: Configurable functions when delivered
Function
Configuration when delivered
Beam coding
Uncoded
Restart interlock
Not configured
External device monitoring (EDM)
Not configured
Muting
Not configured
Complementary information
The device must be reset to the factory settings to change the configuration to the fol‐
lowing functions:
•
External device monitoring (EDM)
•
Restart interlock
All other functions can be changed subsequently without resetting the device to factory
settings.
Further topics
•
"Set to factory settings", page 67
7
CONFIGURATION
66
O P E R A T I N G I N S T R U C T I O N S | deTem4 A/P
8024782/2019-11-19 | SICK
Subject to change without notice