Further topics
•
•
7.8
Configuring external device monitoring (EDM)
Prerequisites
•
External device monitoring can only be configured when the wiring has been cor‐
rectly performed
Approach
1.
Disconnect the device from the voltage supply.
2.
Make sure that the wiring has been performed correctly and that the contactor has
dropped out so that 24 V is present at the EDM input when the device is switched
on
3.
Switch on the voltage supply.
✓
The device is in configuration mode, the INFO LED flashes green.
✓
Diagnostic LED 1 flashes white and signals that the external device monitoring has
been configured.
✓
External device monitoring is active. The wiring must remain at the connection to
which it was connected during configuration.
4.
If necessary: to configure the restart interlock, press the reset pushbutton for
between 1 and 3 s, then release it. If diagnostic LED 4 flashes white, the restart
interlock has been configured.
5.
Disconnect the device from the voltage supply.
✓
The device can now be put into operation.
To deactivate external device monitoring, reset the active unit to the factory settings.
Complementary information
External device monitoring is deactivated on delivery.
Further topics
•
"External device monitoring (EDM)", page 39
•
7.9
Configuring application diagnostic output
Overview
The application diagnostic outputs are configured automatically:
The following signals can be output over the application diagnostic output:
•
Weak signal
•
Reset required
•
Muting status
•
Override required
A signal can be output on both the system and extension connections.
7
CONFIGURATION
72
O P E R A T I N G I N S T R U C T I O N S | deTem4 A/P
8024782/2019-11-19 | SICK