Complementary information
You can also change the beam coding later. You do not need to reset the protective
device to the factory settings to do this.
If code 1 or code 2 is configured, the beam coding DIP switches do not need to be con‐
sidered during the parity test.
Further topics
•
"Protection against interference from systems in close proximity to each other",
page 25
•
7.5
Configuring muting
Overview
Muting is configured using the DIP switches 1, 2 and 4 (row A) on the active unit.
Depending on arrangement of the muting sensors, cross-muting or exit monitoring can
be configured and the protective effect of the multiple light beam safety device can be
temporarily bypassed. A muting signal can be moved from the extension connection to
the system connection.
Prerequisites
•
SP2 system plug
Configuring muting
OFF
uncoded
code 1
code 2
ref.conf.
ON
1 2 3 4
O F F
1 2 3 4
O F F
1 2 3 4
O F F
1
O
N
2
A
B
C
D
1 2 3 4
O F F
Figure 42: DIP switch for muting on the SP2 system plug
Table 23: DIP switch and muting
DIP switch 1
(row A)
DIP switch 2
(row A)
DIP switch 3
(row A)
DIP switch 4
(row A)
Function
Off
Off
Off
Off
Muting deactivated (deliv‐
ery condition)
Off
On
Off
Off
Cross muting
CONFIGURATION
7
8024782/2019-11-19 | SICK
O P E R A T I N G I N S T R U C T I O N S | deTem4 A/P