Active unit
Display of the configuration mode
•
INFO LED:
Ö
Green
•
OSSD LED:
O
Red
o
LED off.
Ö
LED flashes.
O
LED illuminates.
Provided that the device is in configuration mode, you can make further changes to the
configuration:
•
Configuring the restart interlock
Quit configuration mode
b
Briefly interrupt the voltage supply, then switch it back on.
7.4
Configuring beam coding
Overview
The beam coding “uncoded” allows for particularly short response times.
To protect against interference from systems in close proximity to each other, code 1
and code 2 must be used.
Configuring beam coding
The beam coding is configured using 2 DIP switches. The DIP switches are located on
the inside of the system plug.
1
O
N
2
OFF
uncoded
code 1
code 2
ref.conf.
ON
1
O
N
2
D
Figure 41: Configuring beam coding
Table 22: DIP switches and beam coding
DIP switch 1 (row D)
DIP switch 2 (row D)
Function
Off
Off
Uncoded (fast response time,
delivery status)
On
Off
Code 1 (protection against
interference from systems in
close proximity to each other)
Off
On
Code 2 (protection against
interference from systems in
close proximity to each other)
On
On
Reset to factory settings
The beam coding is indicated when the protective device is switched on:
•
Uncoded: INFO LED does not flash yellow
•
Code 1: INFO LED flashes yellow once
•
Code 2: INFO LED flashes yellow twice
7
CONFIGURATION
68
O P E R A T I N G I N S T R U C T I O N S | deTem4 A/P
8024782/2019-11-19 | SICK