WARNING
Persons or parts of the body to be protected may not be recognized or not recognized in
time in case of non-observance.
Before commissioning the machine or vehicle, check the configuration of the protective
fields,
see "Checklist for initial commissioning and
.
b
Check the configured protective fields.
NOTE
3
or the warning fields
2
extend all the way to a wall or another
object (pillar, neighboring machine, shelf), there should be a distance of 100 mm
between the protective field or warning field and the object to prevent false triggering
1
.
Figure 64: Configuring the protective field and warning field
DANGER
Persons or parts of the body to be protected may not be recognized or not recognized in
time in case of non-observance.
If it is possible to access a narrow strip between the protective field and a wall or
another object, this strip must be protected using additional measures (e.g., fence or
floor protection).
b
Secure unprotected areas.
Further topics
•
7.12.2
Importing and exporting field sets and fields
Overview
If you need identical field sets or fields across different projects, you can export entire
field sets or individual fields out of one project and import them into another project.
7
CONFIGURATION
90
O P E R A T I N G I N S T R U C T I O N S | S300
8010948/ZA21/2020-06-18 | SICK
Subject to change without notice