Fixed setting: The device uses the set cycle time as a maximum, regardless of the
object surface. The output rate of the measured values corresponds to the set
value and remains constant.
NOTE
If the remission properties of the object are not sufficient to perform a valid mea‐
surement, the device outputs the value of an incorrect measurement,
in case of incorrect measurements", page 38
>
Measurement
>
>
Default settings
>
>
Cycle time
>
Parameter
Factory setting
Auto, 0.3 ms, 0.5 ms, 1 ms, 5 ms, 10 ms
Auto
8.3.2.2
Measured value filter
The measured value filters are used to optimize the signal diagram in order to simplify
the evaluation by the control system, e.g., for regulation tasks.
Available measured value filters:
•
Average filter The average filter carries out a moving averaging of the measured
values. The average filter is suitable for smoothing a noisy signal diagram. This
improves the repeatability of the measurement.
•
Median filter: The moving median filter sorts the measured values according to
their size and selects the middle value from a sequence. The median filter is suit‐
able for excluding individual outliers from the calculation of an average value.
Both types of filter affect the response time of the distance sensor.
OPERATION VIA DISPLAY
8
8019642/18JN/2020-07-01 | SICK
O P E R A T I N G I N S T R U C T I O N S | OD1000