Figure 8: Shield connection in plastic housings
NOTE
Use an appropriate earthing method to prevent equipotential bonding currents flowing
through the cable shield. If necessary, ground currents on the EtherNet/IP cabling can
be prevented by using an EtherNet/IP adapter (part no. 2044264).
6.3
Connecting the device electrically
NOTE
The connection diagram, and information on inputs and outputs, can be found on the
side plate on the device.
NOTICE
All electrical circuits must be connected to the device with safety extra-low voltage
(SELV or PELV).
1.
Ensure that the voltage supply is not connected.
2.
Connect the device according to the connection diagram.
3.
Observe the wiring instructions,
see "Wiring instructions", page 18
1
4
3
5
2
L+
1
brn
M
3
blu
Q
1
/C
4
blk
Q
A
/Q
2
/¯
Q
1
2
wht
In1
5
gra
Figure 9: Connection diagram, 5-pin male connector
Table 2: Legend for connection diagram
Contact
Identification
Wire color
Description
1
L+
Brown
Supply voltage: +18 ... +30 V DC
2
Q
A
/Q
2
/Q
1
White
Output 2: analog output / digital output 2
(push-pull stage) / not Q
1
3
M
Blue
Supply voltage: 0 V
6
ELECTRICAL INSTALLATION
20
O P E R A T I N G I N S T R U C T I O N S | OD1000
8019642/18JN/2020-07-01 | SICK