Minimum
1
Maximum
3
4
1
0
2
Figure 19: Object between device and background (normally closed – Low Active, PNP)
1
Minimum
2
Tolerance around switching point: ± 4.0 mm
3
Maximum
4
Switching point (reference background)
>
I/O interface
>
>
Q1 output
>
>
ObSB
>
Parameter
Factory setting
Q1 teach-in:
Q1, Q1 not
-
Manual Q1 teach-in:
-1,000.0 mm ... +1,000.0 mm
+400 mm
Q1 active status:
High, Low
High
Q1 hysteresis:
0000.0 mm ... +0100.0 mm
+1.0 mm
Q1 ObSB tolerance
-1,000.0 mm ... +1,000.0 mm
+4.0 mm
Delay mode:
Off, switch-on delay, switch-off delay, switch-on/switch-off delay, 1
shot
Off
Time for delay mode:
0000 ms ... 9,999 ms
100 ms
8.4.1.5
Alarm
The alarm function is only available in the
Advanced
user level. A constant switching sig‐
nal is output at the output of the device while no measurement is possible. This func‐
tion can be used to evaluate the measured value at the analog output, for example.
>
I/O interface
>
>
Q1 output
>
>
Alarm
>
Parameter
Factory settings
Alarm
Off
8.4.1.6
Signal level warning
The signal level warning function is only available in the
Advanced
user level.
8
OPERATION VIA DISPLAY
44
O P E R A T I N G I N S T R U C T I O N S | OD1000