(5)SON off, RES on, and EM2 off check during the ABS transfer
When the ABS transfer mode is turned on to start transferring and then SON is turned off, RES is turned on,
or EM2 is turned on before the 19th ABST is turned on, [AL. 17 ABS time-out warning] occurs, regarding it as a
transfer error.
Checksum error
If the checksum error occurs, the programmable controller should retry transmission of the absolute position data.
Using the ladder check program of the programmable controller, turn off ABSM. After a lapse of 10 ms or longer,
turn off SON (off time should be longer than 20 ms) and then turn it on again. If the absolute position data transmission
fails even after retry, process the ABS checksum error.