36
3. Primary operation
Primary operation
3.6 The basic operation procedure for communication mode (
,
P.79=3)
● In communication mode, the user can set
parameters, run/stop, and reset the inverter by
communication. Please refer to
P.33
for details.
3.7 The basic operation procedure for Combined mode 1 (
,
P.79=4 )
Steps
Description
1
• In Combined mode 1, the indicating lamp of
will flicker.
Note: For selection and shifting of operation modes, please refer to Section 3.1.
2
• Enter the frequency setting mode, and write the target frequency into the memory.
Note: For the operating procedure of the frequency setting mode, please refer to Section 3.2.
3
• Set the target frequency by
DU03B operation panel
and start the inverter by the
external
terminals
.
• At this time, the indicating lamp of
will flicker which indicated that the motor is
running.
Note: For the operating procedure of the monitoring mode, please refer to Section 3.2.
4
• Turn off STF or STR, and then the motor will decelerate, till it stops.
• The indicating lamp of
will not turn off until the inverter has stopped putting out
voltages.
3.8 The basic operation procedure for Combined mode 2 (
, P.79=5)
Steps
Description
1
• In Combined mode 2, the indicating lamp of
will flicker.
Note: For selection and shifting of the operation mode, please refer to Section 3.1.
2
•
The
target frequency
is set by
external terminals
:
• If the target frequency is set by the input signal across terminal 4-5, please refer to P.39 in
Chapter 4.
• If the target frequency is set by multi-speed stage levels, please refer to P.4 in Chapter 4.
• If the target frequency is set by the input signal across terminal 2-5, please refer to P.38 in
Chapter 4.
3
• Press down
FWD
or
REV
, and then the motor start running. At this time, the indicating lamp of
will flicker, which indicates that the motor is running.
Note: 1. For the operating procedure of the monitoring mode, please refer to Section 3.2.
2. In case the motor is running, the frequency setting mode is also valid, and thus the target frequency
can be changed to regulate the motor speed.
4
• After pressing down
STOP
RESET
, the motor will decelerate, till it stops.
• indicating lamp of
will not turn off until the inverter has stopped putting out
voltages.