4. Parameter description
Parameter
4.4
Multi-speed (P.4~P.6, P.24~P.27, P.142~P.149)
P.4 “speed 1(high speed)”
P.5 “speed 2(medium speed)”
P.6 “speed 3 (low speed)”
P.24~P.27 “speed 4 to 7”
P.142~P.149 “speed 8 to 15”
Related parameters
P.2
“
Minimum frequency
”
P.1
“
Maximun frequency
”
P.29
“
Acceleration /deceleration
curve selection
”
P.80~P.84 , P.86
P.79
“
Operation mode selection
”
“
Multi-function terminals selection
”
Parameter
Factory setting
Setting range
Remarks
4
60Hz
0~400Hz (Note 3)
---
5
30Hz
0~400Hz (Note 3)
---
6
10Hz
0~400Hz (Note 3)
---
24~27
9999
0~400Hz, 9999 (Note 3)
9999, is not chosen
142
0Hz
0~400Hz (Note 3)
---
143~149
9999
0~400Hz, 9999 (Note 3)
9999, is not chosen
<Setting>
• If all the setting values of P.24~P.27 and P.142~P.149 are not 9999, ‘16-speed operation’ is active. It
means that with the combination of RL, RM, RH and REX, there are 16 kinds of speeds in all. For
the setting of the target frequency of the inverter, please refer to the figure below.
RL
RH
RM
REX
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
(High speed)
speed1
(Medium speed)
Speed 2
(Low speed)
Speed 3
Speed
4
Speed
5
Speed
6
Speed
7
Speed
8
Speed
9
Speed
10
speed
11
Speed
12
Speed
13
Speed
14
Speed
15
O
ut
pu
t f
re
qu
en
cy
Speed
0