99
4. Parameter description
Parameter
Parameter
Factory setting
Setting range
Remarks
125
0
(Note)
---
126
9999
0~39, 9999
0~39
The
function
is
the
same
with
‘multi-function control terminal’. For
detailed description, please refer to
P.80~P.84, P.86.
127
9999
0~39, 9999
128
9999
0~39, 9999
9999 Function invalid
129
9999
0~10, 9999
0~10
The
function
is
the
same
with
multi-function output relay (ABC). For
detailed description, please refer to P.85.
130
9999
0~10, 9999
9999 Function invalid
Note: 1. The value of P.125 indicates the type of the expansion board. 0: communication expansion board
(
include
SE-CB01
、
SE-CB02
、
SE-CB03
)
, 1: I/O expansion board (SE-EB01), 2: current source expansion board
(SE-IB01), 4.
Profibus
expansion board (SE-PD01), 6.
DeviceNet
expansion board (SE-DN01),
7: No
expansion board. When there is any expansion board is connected to the main machine, the inverter will
detect what kind of expansion board it is. If the first detection result is different from the next one; or they
are the same, but not the three types referred, an alarm will be output, and the screen will display
. If
no expansion board is detected, the corresponding parameters are forbidden to read or write, but they are
restored to the default values when we read out P.998 or P.999 and rewrite in them.
2. On the details of the expansion board, refer to optional accessories of Appendix 5.
4.42 Zero-speed Function (P.151~P.152)
P.151 “Zero-speed control function selection”
P.152 “Voltage instruction
at
zero-speed control”
Related parameters
P.13
“
Starting frequency
”
●You must set the value of P13 is zero, when you use to this function.
Parameter Factory setting
Setting range
Remarks
151
0
0~1
0
There are no output when zero-speed
1
Control by DC (Note 1)
152
5%
0~30%
(Note 2)
Note: 1.The output mode selected by the value of P.151, when P.151 is 0 then there is no output, when P.151 is 1
then the value of P152 which is voltage output dc voltage as keep torque.
2. Suppose that P.152=6%, then the output voltage is P.19*6% when zero-speed.
3. This function is valid in V/F curve. It means P.300 must be set to 0.