Appendix 1 Parameter list
Parameter list
Note: 1.The torque boost, motor rated current and the stator resistance values are in the table as follows:
Inverter Type
P. 0
P. 9(A)
SE2-021-0.4KW
6
3.0
SE2-021-0.75KW
6
5.0
SE2-021-1.5KW
4
8.0
SE2-021-2.2KW
4
11.0
SE2-023-0.4KW
6
3.0
SE2-023-0.75KW
6
5.0
SE2-023-1.5KW
4
8.0
SE2-023-2.2KW
4
11.0
SE2-023-3.7KW
4
17.5
SE2-023-5.5KW
3
24.0
SE2-023-7.5KW
3
33.0
SE2-043-0.4KW
6
1.5
SE2-043-0.75KW
6
2.6
SE2-043-1.5KW
4
4.2
SE2-043-2.2KW
4
6.0
SE2-043-3.7KW
4
9.0
SE2-043-5.5KW
3
12.0
SE2-043-7.5KW
3
17.0
SE2-043-11KW
2
23.0
SE2-021-0.2KW
6
1.6
2. The default value is due to the set value of P.189. When P.189=0, the default value is 60Hz, which is
applied to the 60Hz system. When P.189=1, when default value is 50Hz, which is apply to the 50Hz
system.
3. The minimum value and setting range of all the frequency related parameters can choose by P.187. You can
refer to Appendix 6 for details.
Parameter
number
Name
Setting range
Minimum
setting unit
Default
value
User setting
value
Reference
page
Speed
control
proportion
coefficient
0~2000%
1%
100%
P120
Speed
control
integral
coefficient
0~20s
0.01s
0.30s
P120
Refer to Chapter 4
---
---
---
P121
Refer to Chapter 4
---
---
---
P121
Alarm history clear
Refer to Chapter 4
---
---
---
P121
Inverter reset
Refer to Chapter 4
---
---
---
P122
Restoring all parameters to
default values
Refer to Chapter 4
---
---
---
P122
Restoring some parameters to
default values
Refer to Chapter 4
---
---
---
P122