4. Parameter description
Parameter
• If you need Sensorless vector control, you should set P.300 to 3.
Note: 1. Motor capacity and inverter capacity must be with grade or sub-grade.
2. If P.187=1, the sensorless vector control function is invalid.
3. To do auto measurement function, such as permitting motor rotation, set P.301 to 1
(Dynamic measurement), then it should be made load off the motor completely. Such as loading conditions
don't allow the case which the motor rotation when Auto-tuning automatic measurement function, please
set P.301 to 2 (Static measurement).
4. Sensorless vector control: measurement by automatic (Auto-tuning) function to enhance the control
performance. Set the motor parameters or do auto measurement function before set P.300 to 3, in order to
increase the control accuracy
4.64 Motor Parameter (P.302~P.312)
P.302 “Motor rated power”
P.303 “Motor poles”
P.304 “Motor rated voltage”
P.305 “Motor rated frequency”
P.306 “Motor rated current”
P.307 “Motor rated rotation speed”
P.308 “Motor excitation current”
P.309 “Stator resistance”
P.310 “Rotor resistance”
P.311 “Leakage inductance”
P.312 “Mutual inductance”
Parameter
Factory setting
Setting range
Remarks
302
0
0~160
---
303
4
0~8
---
304
220/440V
0~440V
---
305
50Hz
0~400Hz
P.189=1
60Hz
P.189=0
306
Determined by horsepower
0~500A
---
307
1410r/min
0~9998 r/min
P.189=1
1710 r/min
P.189=0
308
Determined by horsepower
0~500A
---
309
Determined by horsepower
0~9998
---
310
Determined by horsepower
0~9998
---
311
Determined by horsepower
0~9998
---
312
Determined by horsepower
0~9998
---