4
2.
Introduction of Shihlin Inverter
Introduction of Inverter
2.2 Common specification (Inverter characteristics)
Control method
SVPWM control, V/F control, facility vector control, Sensorless vector
control.
Output frequency range
0.2~1000Hz (The starting frequency setting range is 0~600Hz). Please
refer to P.187 in Chapter 4.
Resolution for
setting frequency
Digital
setting
When P.187=0, if the frequency set value is below 100Hz, the resolution
will be 0.01Hz. If the frequency set value is above 100Hz, the resolution
will be 0.1Hz. When P.187=1, the resolution of frequency will be 0.1Hz.
Analog
setting
When setting DC 0~5V signals, the resolution will be 1/500;
When setting DC 0~10V or 4~20mA signals, the resolution will be
1/1000.
Output frequency accuracy 0.01Hz
Voltage / frequency output
characteristics
Base frequency voltage
(P.19), base frequency (P.3) can be arbitrarily set
in
available range.
Constant torque model,
applicable load model
can be selected (P.14).
Start torque
150% (1Hz): When the sensorless vector control is started.
Torque boost
The torque boost setting range is 0~30% (P.0), auto boost, slip
compensation.
Acceleration/deceleration
curve characteristics
The resolution (0.01s/0.1s) of acceleration/deceleration time (P.7, P.8) is
switched by P.21
. The setting range has
0~360s or 0~3600s
for selection.
And different acceleration/deceleration curve model can be selected
by
P.29
.
DC braking
The DC braking action frequency is
0~120Hz
(P.10); the DC braking
time is 0~60 Seconds (P.11); and the DC braking voltage is 0~30%
(P.12). Linear braking and Idling braking selection (P.71).
Stalling protection
The stalling protection level can be set to 0~400% (P.22).
Target frequency setting
Operation panel setting;
DC 0~5V signal setting, DC 0~10V signal setting and DC 4~20mA
signal setting, 2 voltage input or one voltage and one current input can
be selected;
Multi-speed stage levels setting; Communication setting.
PID control
Please refer to P.170~P.183 in Chapter 4.
Multi-function control
terminals
Motor starting (STF, STR), the second function (RT), the 16-speed
operation (RL, RM, RH, REX), external thermal relay (OH), reset
(RES)
, etc. (they can be set by the user with P.80~P.84, P.86)
Multi-
function
output
terminals
Multi-function
output terminals
(SO, SE)
P.40
Inverter running (RUN), output frequency detection (FU), Up to
frequency (SU), overload
alarm
(OL), zero current detection
(OMD), alarm (ALARM), Section detection (PO1), Periodical
detection (PO2), and Pause detection (PO3), Inverter output (BP),
Commercial power-supply output (GP).
Multi-function
output relay
P.85
Multi function
analogy meter
Multi-function DC (0~10V)(AM)
Output: output frequency, output current (P.54).