The Zone profile
Page 78
FlexPS Product Guide
If the A-side of the processor is not used, remove the shunt from T12. An A-side supervision
alarm should be declared. Replace the shunt on T12 and the A-side supervision alarm should
clear.
If a properly terminated sensor cable is connected to the B-side, place a shunt on T13. A
B-side supervision alarm should be declared. Remove the shunt from T13 and the B-side
supervision alarm should clear.
If the B-side of the processor is not used, remove the shunt from T13. A B-side supervision
alarm should be declared. Replace the shunt on T13 and the B-side supervision alarm should
clear.
PASS ____ FAIL____
•
Audio
- On the UCM Status window, activate the Audio Monitor for the A-side. Have a tester
create some fence noise in the selected zone while listening to the connected speaker.
Activate the Audio Monitor for the B-side. Have a tester make some fence noise in the
selected zone while listening to the connected speaker.
PASS ____ FAIL____
•
Self-test
- Activate the self-test for the A-side. The processor performs electronic self-tests of
the A-side detection (cut and climb). The first test causes a cut alarm, and the second test
causes a climb alarm. The test can take up to a minute, depending on the Time settings.
Activate the self-test for the B-side. The processor performs electronic self-tests of the B-side
detection (cut and climb). The first test causes a cut alarm, and the second test causes a climb
alarm. The test can take up to a minute, depending on the Time settings.
PASS ____ FAIL____
•
Auxiliary device inputs
- For Local control mode the Aux inputs activate the system self-test
and the Audio listen-in feature. In this case, activate the appropriate switch, and verify that the
specified event occurs (self-test or Audio ON/OFF). Repeat for both cable sides.
For Remote control mode, the Aux inputs serve as auxiliary device inputs to the host system.
In this case, activate the connected device, and verify the status change is reported by the
host system. Repeat for Aux 2.
PASS ____ FAIL____
•
Relay outputs
- For Local control mode the relay outputs are used to report events. Cause an
event, and verify that the specified relay activates for a minimum of the relay hold time. Repeat
this procedure for each specified event (in the Output Configuration field).
For Remote control mode, the relays serve as output control points for the host system. Send
an activation command from the host system to one of the relays and verify that the relay
activates. Repeat this procedure for each relay.
PASS ____ FAIL____
The Zone profile
Senstar strongly recommends creating a zone profile for each FlexPS sensor zone at your site. To
create a zone profile, connect the UCM to the processor. Open a magnitude response plot, and
select the Disable Filter Reset After Alarms check box. Have a tester move along the zone,
tapping each fence panel three times, while recording the plot. After tapping the final fence panel
in the zone, stop the recording and save the UCM plot. This plot file provides a record of the
sensor’s response immediately after calibration. This can be compared to future response plots for
maintenance or troubleshooting activities.