SEC 3120 16-bit Modbus Manual
Page 34 Of 46
Sensor Electronics Corporation
For Version 1.2 and above
December 2012
P/N 1580282, Rev. 1, 20121228
Table 11: Function Code 06 Preset Holding Register
Internal
Register
Address
Holding
Register
Address
Function Code 06- Preset Sensor Register Description
(Data bits and Parameter Specifics)
x = sensor number, or
0 to apply to all sensors.
2x03
42x04
*Scaled Integer Sensor Alarm Low Set Point.
4000 Hex must be added as a password to write value.
2x04
42x05
*Scaled Integer Sensor Alarm Mid Set Point.
4000 Hex must be added as a password to write value.
2x05
42x06
*Scaled Integer Sensor Alarm High Set Point.
4000 Hex must be added as a password to write value.
2x06
42x07
*Scaled Integer Sensor Calibration Value.
4000 Hex must be added as a password to write value.
2x10
42x11
**Sensor Zone ID.
4000 Hex must be added as a password to write value.
2x39
42x40
**Start Sensor Self Test Operation (00FF Hex Start, 0 stop)
4000 Hex must be added as a password to write value.
*The real value must be multiplied by the Gas Factor (2x08).
i.e. 2.12 ppm to set low set point register: scaled low set point = 2.12 X 10 (from 2x08) =
212 (00D4 Hex). When the password is added (4000 Hex) the complete value needed to
write the register and change the low set point then is 40D4 Hex.
** Zone ID (2010/42012) and Self Test (2039/42040) may be written to in region zero
(apply to all sensors) for a 3120 with two or more sensors attached, when the sensor role
is either "Unique" or "Identical" modes, but NOT when in "Single" sensor role- an
exception message will be generated and sent back to the master in place of a message
echo. If sensor role is "Identical", values must also be identical!
Internal
Register
Address
Holding
Register
Address
Function Code 06- Preset Unit Register Description
(Data bits and Parameter Specifics)
2911
42912
New 3120 Unit Clock Month Value.
4000 Hex must be added as a password to write value.
2912
42913
New 3120 Unit Clock Day Value.
4000 Hex must be added as a password to write value.
2913
42914
New 3120 Unit Clock Year Value.
4000 Hex must be added as a password to write value.
2914
42915
New 3120 Unit Clock Hours Value.
4000 Hex must be added as a password to write value.
2915
42916
New 3120 Unit Clock Minutes Value.
4000 Hex must be added as a password to write value.
2916
42917
New 3120 Unit Clock Seconds Value.
4000 Hex must be added as a password to write value.
2917
42918
Set New 3120 Unit Clock NOW (00FF Hex set, 0 clear).
4000 Hex must be added as a password to write value.
Summary of Contents for SEC 3000
Page 15: ...Doc 1460003 Rev A Operation Manual SEC 3000 Electro Chemical Gas Sensor Page 12 of 13 ...
Page 54: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 4 SEC 3100 SEC Millenium Mounting ...
Page 55: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 5 SEC 3100 SEC 3000 Mounting ...
Page 56: ...TB 1 J1 TB 2 J2 1 6 1 6 1 4 1 6 TB 5 J5 TB 6 J6 ...
Page 148: ...SEC 3120 Wiring TB 1 P3 TB 2 P6 1 6 1 6 1 2 3 4 1 2 3 4 7 6 5 4 3 2 1 TB 3 P1 TB 4 P5 ...
Page 156: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 399: ...SEC P N 1460014 Rev ECO A 000209 Page 11 of 26 ...
Page 400: ...SEC P N 1460014 Rev ECO A 000209 Page 12 of 26 ...
Page 431: ...Part Number 1460005 Revision C ...
Page 433: ...Part Number 1460005 Revision C ...
Page 434: ...Part Number 1460005 Revision C ...
Page 435: ...Part Number 1460005 Revision C ...