III. OPERATION
Installation and Startup
Warning: The user shall be made aware that if the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be impaired.
The first step in the installation process is to establish a mounting location for the SEC MILLENIUM. Select a
location that is typical of the atmosphere to be monitored or close to the anticipated source of a dangerous
gas.
It is very important that the SEC MILLENIUM be properly located to enable it to provide maximum
protection. The most effective number and placement of sensors vary depending on the conditions of the
application. When determining where to locate sensors the following factors should be considered.
How rapidly will the gas diffuse into the ambient air? Select a location for the sensor that is close to the
anticipated source of a gas leak.
Wind or ventilation characteristics of the immediate area must also be considered. Movement of air may
cause gas to accumulate more heavily in one area than in another. The detector should be placed in the
areas where the most concentrated accumulation of gas is anticipated. For outdoor applications with
strong wind conditions, it may require the sensors to be mounted closer together and on the down wind
side, to the anticipated area of a gas leak. Also take into consideration for indoor applications, the fact
that many ventilation systems do not operate continuously.
The sensor should be accessible for maintenance.
Excessive heat or vibration can cause premature failure of any electronic device and should be avoided
if possible.
Follow all national and local installation codes and practices
.
RgasD = 1.53 (Relative density of gas (CO2) referenced to air =1. Indicates how many times a gas is
heavier than air at the same temperature).
Normal constitute of air is about 300 PPM of CO2.
The SEC MILLENIUM has a ¾” NPT threaded connector for mounting the detector to a junction box. SEC
can provide a junction box with terminals for this purpose.
A user-supplied junction box can be used providing it has the appropriate sized NPT conduit entries. The
junction box must be suitable for use in the application and location in which it is being installed. After the
device has been installed, a calibration is required. Refer to the Calibration section of this manual.
Wiring connections
Red wire:
18 to 32 VDC
Black wire: DC Common
Blue wire:
4 to 20 mA output
White wire: Smart Calibration Wire (data wire)
Earth Ground: Male 10-32 Stud on SEC Millenium cap, see figure 1.
Wire sizing:
0 to 500 feet, recommended wire gauge size 16 AWG
501 to 1000 feet, recommended wire gauge size 14 AWG
Shielded cable is recommended. Wiring should be installed in medal conduit with no other cabling in the
same conduit.
!
Summary of Contents for SEC 3000
Page 15: ...Doc 1460003 Rev A Operation Manual SEC 3000 Electro Chemical Gas Sensor Page 12 of 13 ...
Page 54: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 4 SEC 3100 SEC Millenium Mounting ...
Page 55: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 5 SEC 3100 SEC 3000 Mounting ...
Page 56: ...TB 1 J1 TB 2 J2 1 6 1 6 1 4 1 6 TB 5 J5 TB 6 J6 ...
Page 148: ...SEC 3120 Wiring TB 1 P3 TB 2 P6 1 6 1 6 1 2 3 4 1 2 3 4 7 6 5 4 3 2 1 TB 3 P1 TB 4 P5 ...
Page 156: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 399: ...SEC P N 1460014 Rev ECO A 000209 Page 11 of 26 ...
Page 400: ...SEC P N 1460014 Rev ECO A 000209 Page 12 of 26 ...
Page 431: ...Part Number 1460005 Revision C ...
Page 433: ...Part Number 1460005 Revision C ...
Page 434: ...Part Number 1460005 Revision C ...
Page 435: ...Part Number 1460005 Revision C ...