Relay Menu
Selecting Enter will advance to the following menu.
Arrow down to the next screen will be
Select the Alarm Relay (LOW, MID, HI, FAULT) that is to be configured using the down arrow. Once the
cursor is on the correct alarm relay, hold the magnet over Enter. The example LOW will be used. The
same operations can be used to set the MID, HI, or FAULT relays.
Select Enter
Select Enter
Using the Up and Down arrows the operator can change the ON delay time for the relay to actuate after the
alarm threshold has been exceeded. The time is measured in seconds (0-255). Once the correct time is
displayed select Enter to accept the new value. Then Exit the menu and proceed on to the next selection.
In this example the Low alarm relay will actuate 30 seconds after the Low set point is exceeded.
CALIBRATION
ALARM
* RELAY
* LOW
MID
HI
* FAULT
EXIT
* LOW
MID
HI
* ON DLY LOW 0
OFF DLY
ENERGIZED
EXIT
* ON DLY LOW 0 *
OFF DLY
ENERGIZED
EXIT
* ON DLY LOW 30
OFF DLY
ENERGIZED
EXIT
Summary of Contents for SEC 3000
Page 15: ...Doc 1460003 Rev A Operation Manual SEC 3000 Electro Chemical Gas Sensor Page 12 of 13 ...
Page 54: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 4 SEC 3100 SEC Millenium Mounting ...
Page 55: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 5 SEC 3100 SEC 3000 Mounting ...
Page 56: ...TB 1 J1 TB 2 J2 1 6 1 6 1 4 1 6 TB 5 J5 TB 6 J6 ...
Page 148: ...SEC 3120 Wiring TB 1 P3 TB 2 P6 1 6 1 6 1 2 3 4 1 2 3 4 7 6 5 4 3 2 1 TB 3 P1 TB 4 P5 ...
Page 156: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 399: ...SEC P N 1460014 Rev ECO A 000209 Page 11 of 26 ...
Page 400: ...SEC P N 1460014 Rev ECO A 000209 Page 12 of 26 ...
Page 431: ...Part Number 1460005 Revision C ...
Page 433: ...Part Number 1460005 Revision C ...
Page 434: ...Part Number 1460005 Revision C ...
Page 435: ...Part Number 1460005 Revision C ...