Alarm Menu
Enter
Select the Alarm Relay (LOW, MID, HI, FAULT) using the down arrow. Once the cursor is on the alarm
relay you wish to configure, hold the magnet over Enter. The example LOW will be used. The same
operations can be used to set the MID, HI or FAULT relays.
Selecting Enter will display the following screen allowing the alarm set point to be
programmed. Using the Up and Down arrows will change the set point. Once the correct set point is
displayed select Enter and the new value will be accepted.
Arrow Down
Selecting Enter will allow the operator to change the operation of the relay operation from Non-Latching
(NORMAL) to Latching (LATCHING) or to Audible (AUDIBLE).
If the relays are set to Latching or Audible, the magnet can be used to reset (unlatch or silence) the relays
by selecting any magnetic pickup switch UP arrow, DOWN arrow or ENTER.
CALIBRATION
* ALARM
RELAY
* LOW
MID
HI
* ALARM LOW 4
LATCH
ACTIVE
EXIT
* ALARM LOW 2 *
LATCH
ACTIVE
EXIT
CONFIGURING PROCESS
------ WAIT -------
* ALARM LOW 2
LATCH
ACTIVE
EXIT
ALARM LOW
* LATCH NORMAL
ACTIVE
EXIT
* FAULT
EXIT
Summary of Contents for SEC 3000
Page 15: ...Doc 1460003 Rev A Operation Manual SEC 3000 Electro Chemical Gas Sensor Page 12 of 13 ...
Page 54: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 4 SEC 3100 SEC Millenium Mounting ...
Page 55: ...Part Number 3100 EXP MANUAL REV 11 20141007 FIGURE 5 SEC 3100 SEC 3000 Mounting ...
Page 56: ...TB 1 J1 TB 2 J2 1 6 1 6 1 4 1 6 TB 5 J5 TB 6 J6 ...
Page 148: ...SEC 3120 Wiring TB 1 P3 TB 2 P6 1 6 1 6 1 2 3 4 1 2 3 4 7 6 5 4 3 2 1 TB 3 P1 TB 4 P5 ...
Page 156: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 399: ...SEC P N 1460014 Rev ECO A 000209 Page 11 of 26 ...
Page 400: ...SEC P N 1460014 Rev ECO A 000209 Page 12 of 26 ...
Page 431: ...Part Number 1460005 Revision C ...
Page 433: ...Part Number 1460005 Revision C ...
Page 434: ...Part Number 1460005 Revision C ...
Page 435: ...Part Number 1460005 Revision C ...